QTP4B051-18 governs ventilation calculations and surveys, including airflow, velocity, area, air changes, pitot traverses, and static pressure.
View QTP4B051-18 on armypubs.army.mil
QTP4B051-18 contains training guidance, task steps, review questions, performance checklists, and answers for ventilation calculations and surveys. It requires measurement, calibration, recording, calculation, and evaluation of ventilation system parameters.
Velocity (V), area (A) and the airflow volume (Q), or mass flow in cubic feet per minute (cfm). (paragraph 1)
For rectangular areas, it is simply a matter of multiplying the length times the width and dividing by 144. (paragraph 3)
At least 7 duct diameters downstream and one duct diameters upstream from these elements. (paragraph 2)
Static pressure can be measured at the holes drilled in the duct (wall taps) during the baseline survey or with a Pitot tube inserted to the centerline of the duct. (paragraph 3)
Four readings should be taken 90 degrees apart around the duct and the measured static pressure values averaged. (paragraph 2)