AFMAN32-1065_USAFE-AFAFRICASUP governs requirements for electrical grounding, lightning protection, and static protection systems.
Search AFMAN32-1065_USAFE-AFAFRICASUP
View AFMAN32-1065_USAFE-AFAFRICASUP on armypubs.army.mil
The publication defines procedures for grounding and lightning protection systems in USAFE-AFAFRICA and addresses potentially hazardous explosives facilities. It requires scheduled inspections, testing, maintenance, and compliance with the publication’s attachments.
Compliance with the attachments in this publication is mandatory. (paragraph 33-360)
Lightning protection systems installed at Munitions Support Squadrons (MUNSS) sites shall comply with host nation lightning protection system codes and standards, and applicable portions of this supplement.
All incoming utility services should be verified for continuity of grounding and bonding by the service provider every 5 years (i.e., gas, telephone, signal lines, CATV), including government-owned facilities systems. (paragraph 6)
If utility is privatized, this does not apply; however, safety and operational discrepancies and damage should be reported when observed. (paragraph 1)
Where decision authority is the “Authority Having Jurisdiction” or “AHJ”, the Base Civil Engineer is considered the AHJ. (paragraph 6)